Method guide · ASTM F2170

ASTM F2170: measuring relative humidity inside the slab

The in-situ probe test looks below the surface, where a slab keeps the moisture that a floor covering will eventually sit on top of. Here is how it works and how to read it.

ASTM F2170 is the standard test method for determining relative humidity in concrete floor slabs using in-situ probes. Instead of measuring what leaves the surface, it measures the humidity of a small pocket of air sealed inside the concrete at a specified depth, once that air has come into balance with the concrete around it.

How the test works, step by step

  1. Condition the building. The slab and the air above it are brought to the temperature and humidity the space will have in service, and held there for 48 hours before readings are taken.[1]
  2. Lay out the locations. The method calls for three tests in the first 1,000 square feet and at least one more for each additional 1,000 square feet,[1] typically one near the middle of the area and the rest spread toward the edges.
  3. Drill to depth. For a slab that dries only through its top surface, the hole goes to 40% of the slab thickness.[1] Slabs that dry from both faces use a shallower depth set out in the standard.
  4. Clean, sleeve and seal. Dust is removed and a sleeve or liner isolates the measurement pocket from the room air, so the sensor only sees the concrete at depth.
  5. Wait for equilibrium. The drilled hole is left to come to moisture equilibrium, 24 hours in the current method, before a reading counts.[1]
  6. Read and record. Relative humidity and temperature are recorded for each location, along with the ambient conditions, times and any limitations.

Why 40% deep?

A slab-on-grade loses moisture through its top. That leaves a gradient: drier near the surface, wetter lower down. When the slab is covered with flooring, the moisture inside evens out and the top of the slab gets wetter than it was while exposed. Reading at a set fraction of the depth gives a number that better reflects what the underside of the floor covering will experience after installation than a surface reading would. The Slab Lab below shows that gradient.

What it reports
Relative humidity (%) and temperature at each probe location.
What it measures
Moisture condition inside the concrete at a defined depth.
What it needs
Service conditions in the building, drilling access, protected probe locations, time.
What it does not do
Set a pass/fail number. The selected products’ written limits do that.

What an RH reading can and cannot tell you

A reading tells you the relative humidity at that hole, at that depth, at that time, under the conditions recorded. It does not describe every square foot between holes, and it does not predict next month if the HVAC is switched off, irrigation changes or a pipe starts leaking. It also is not a verdict by itself: the same reading can be within one adhesive’s limit and outside another’s.

No universal threshold Flooring and adhesive manufacturers publish their own maximum RH values, and some products require a specific method. Compare results only against the written instructions for the exact products on the job, and the project specification.

Practical notes for the site

Vegas Flooring Outlet’s own page explains how it scopes project-related slab moisture testing, including how the method is confirmed during scope review.

Interactive

The Slab Lab

Open a cut-away slab, insert an in-situ probe to 40% of the slab depth, and watch the readout settle as the air in the hole comes to equilibrium with the concrete around it. In a real ASTM F2170 test that settling period is measured in hours; here it is sped up to a few seconds.

Illustrative animation, not a project reading

What the Slab Lab shows (text version)
  • A slab-on-grade sits on a sub-base and vapor retarder. Moisture moves upward through it and leaves through the top surface.
  • Concrete near the top dries first, so it can feel dry while concrete lower down is still wetter. The blue tint shows that gradient.
  • For a slab drying only through its top, ASTM F2170 places the sensor at 40% of the slab thickness, a depth intended to represent the moisture the slab can redistribute once it is covered.
  • After the hole is drilled and sleeved, the probe needs time for the air in the hole to reach equilibrium before a reading is recorded. The animation compresses that time.
  • The readout bar is an illustration only. It has no units and is not a project reading or a pass/fail limit.

By Vegas Flooring Outlet · Updated

Need F2170 testing scoped for a project?

Vegas Flooring Outlet offers project-related concrete moisture testing before flooring, adhesive or coating work. Share the project address, slab area, selected flooring system, requested method and schedule; the team reviews the scope before confirming a method or an appointment.

Or read how VFO scopes project-related slab testing.

Call 702.685.8880 Start a testing inquiry