Reading results

RH vs MVER: two numbers that do not translate

One is a percentage from inside the slab. The other is a rate of vapor leaving the surface. Both can be right, and they still cannot be swapped for each other.

When people say a slab “tested at” something, the first question is: tested how? An in-situ relative humidity result and a calcium chloride emission rate come from different methods, describe different parts of the slab and use different units. A limit written for one never applies to the other.

Comparison of in-situ RH testing and MVER testing
PropertyIn-situ RH (ASTM F2170)MVER (ASTM F1869)
Question it answersHow humid is the concrete at a set depth?How much vapor leaves the bare surface over time?
Unit% relative humidity (plus temperature)lb per 1,000 sq ft per 24 hours
Where it looksInside the slab, at a depth set by how the slab driesThe prepared surface and the concrete just below it
Time on siteConditioning, then a 24-hour equilibration after drillingConditioning, then 60 to 72 hours under the dome
Surface prepDrilled, cleaned and sleeved holesBare, clean concrete patches
Pass/fail?Neither. Each result is compared with the limit the selected products publish for that specific method.

Timing and units: see F2170 summary and F1869 kit instructions.

Why the manufacturer’s written limit rules

Flooring, adhesives, underlayments, patching compounds and coatings all react to moisture differently. That is why each manufacturer tests its own products and writes its own limits, often naming which method it accepts. A result only means something next to those words. Two practical consequences:

Ask for limits in writing Before testing, collect the current installation instructions and data sheets for every product that will touch or cover the slab. Note the method each one names and its limit. Then you know what to test for, and what to compare against.

Why a slab can “pass” one test and “fail” the other

Because the two tests look at different depths and react to different conditions, they can point in different directions on the same day. A slab with a dry skin and a wetter core can show a modest surface emission rate while the probes at depth read higher. Conditions in the room during an emission test can push the result around as well. That is not a contradiction; it is two instruments answering two questions.

What not to do

Read more about each method: in-situ RH probes and calcium chloride.